Differential Pressure Transmitters

DPT20 Differential Pressure Transmitter

DPT20

Panel-mount differential pressure transmitter for air and non-corrosive gases, ranges up to 0–250 mm WC, with buzzer or 4–20 mA output.

Range
Up to 0–250 mm WC
Accuracy
±0.5 % FS (≥ 0–25 mm WC)
Output
Buzzer or 4–20 mA
Mounting
Panel mounting

Overview

Typical applications: HVAC systems – airflow and filter monitoring, clean rooms – contamination prevention, industrial processes – filter and pump monitoring, building automation – smart ventilation systems.

Key features

  • Easy panel mounting
  • Ranges from 0–10 to 0–250 mm WC, bi-directional
  • Configuration via keys
  • Version with inbuilt buzzer or with 4–20 mA output
  • Push-on connections for 3/16" tubing

Technical specifications

Measurement ranges & outputs
Measuring ranges (order code)0 - 10 / 0 - 25 / 0 - 50 / 0 - 100 / 0 - 150 / 0 - 200 / 0 - 250 mm WC (all ranges bi-directional)
Alarm / outputInbuilt buzzer / 4-20 mA; 0-10 V (optional)
Accuracy (from applied pressure)Ranges ≤ 0 - 10 mm WC: ±1.0 % of FS · ranges ≥ 0 - 25 mm WC: ±0.5 % of FS
Measuring unitsPa & mmWC
Response time500 ms
Over pressureRanges ≤ 50 mm WC: 9 PSI · 100 to 1000 mm WC: 19 PSI
Media compatibilityAir, non-combustible, non-corrosive gases
General
SwitchDigital push button
Power supply & connectivity
Supply voltage12 - 24 VDC
Signal connection3 wire
Load resistance47 to 470 Ω @ 24 VDC
Electrical connectionsScrew terminals
Installation & environment
Process connectionPush-on connection for 3/16" ID tubing
MountingPanel mounting
EnclosureABS

Specifications are subject to change. Please check the current datasheet or ask our team before ordering.

Models and ordering information

ModelDescription
DPT20Ranges 0–10 to 0–250 mm WC (bi-directional); inbuilt buzzer or 4–20 mA output

Applications and industries

  • HVAC systems – airflow and filter monitoring
  • Clean rooms – contamination prevention
  • Industrial processes – filter and pump monitoring
  • Building automation – smart ventilation systems

Application guides

Application Demonstrations

Interactive examples of how this instrument is used. Choose an application, then try the Normal, Warning and Alarm conditions.

Pharma & life sciences

Cleanroom pressure cascade

Maintain airflow from cleaner to less clean rooms and detect when airflow stops.

Illustration: Cleanroom pressure cascade, with numbered measurement points
Illustrative simulation — not live instrument data. The interactive version needs JavaScript.

Illustrative simulation — not live instrument data.

Measurement points

  1. Pressure tap in the cleanroom (+ port, P1)
  2. − port open to the corridor (reference P2)
  3. DPT30 transmitter on the corridor wall
  4. Signal to the BMS, PLC or data logger

Monitoring workflow

  1. The + port is piped to a tap in the cleanroom, the − port is open to the corridor.
  2. The transmitter measures the difference (ΔP = P1 − P2) in Pa or mm WC, with a 500 ms response time.
  3. The value goes out as 4–20 mA, 0–10 V, relay or RS485 Modbus RTU, depending on model and order code.
  4. Alarm versions sound a buzzer at the door; your BMS, PLC or data logger records the trend.

Products used

Monitoring only: the transmitters measure and signal. Room-pressure control and door interlocks are done by your own systems.

HVAC & building services

Air filter monitoring

Track pressure drop across the filter so replacement occurs at the right time.

Illustration: Air filter monitoring, with numbered measurement points
Illustrative simulation — not live instrument data. The interactive version needs JavaScript.

Illustrative simulation — not live instrument data.

Measurement points

  1. + port upstream of the filter
  2. − port downstream of the filter
  3. DPT20 transmitter on the air-handling unit

Monitoring workflow

  1. The + port is connected upstream of the filter, the − port downstream.
  2. The transmitter measures the pressure difference across the filter.
  3. DPT20 is available with an inbuilt buzzer or a 4–20 mA output; DPT50 WM adds RS485 Modbus RTU and USB configuration.
  4. The BMS trends the value and raises a maintenance alarm at your limit.

Products used

Filter pressure values and the replacement limit are illustrative; use the filter manufacturer's data.

Related products

Enquiry

Ask about the DPT20 Differential Pressure Transmitter

Tell us what you need to measure, the range and the installation. Our technical team will reply with a recommendation and quotation.