Polwax Global

CO₂ & CO Transmitters

CM50 CO (Carbon Monoxide) Transmitter

CM50

Industrial carbon monoxide gas detector and transmitter, 0–1000 or 0–2000 ppm, ±5 ppm accuracy, for car parks, tunnels and plant rooms.

Range
0–1000 / 0–2000 ppm
Accuracy
±5 ppm
Outputs
4–20 mA, 0–10 V, RS485
Supply
10–30 V DC

Overview

Available as 2 versions: CM50-101 and CM50-102.

Typical applications: underground parking garages, tunnels, mechanical & boiler rooms, industrial plants, commercial buildings.

Key features

  • Ranges 0–1000 or 0–2000 ppm
  • Accuracy ±5 ppm, resolution 1 ppm
  • 4–20 mA, 0–10 V or RS485 Modbus RTU output
  • Optional OLED display
  • Sensor lifespan up to 5 years

Technical specifications

Measurement ranges & outputs
Measurement range0 - 1000 ppm (code 101) / 0 - 2000 ppm (code 102)
Accuracy±5 ppm
Resolution1 ppm
Response time≤30 seconds
Repeatability≤2 % of signal value
Zero drift±3 ppm
Long-term drift≤2 %
Output (order code)0-10 V, RS485, 4-20 mA
Sensor lifespanUp to 5 years
General
DisplayOptional OLED display
Power supply & connectivity
Power supply10–30 V DC
Installation & environment
Installation methodWall-mounted / conduit-mount
Operating temperature-20 °C to 50 °C
Operating humidity15–90 % RH (non-condensing)
Pressure range90–110 kPa

Specifications are subject to change. Please check the current datasheet or ask our team before ordering.

Models and ordering information

ModelDescription
CM50-1010–1000 ppm measurement range
CM50-1020–2000 ppm measurement range

Applications and industries

  • Underground parking garages
  • Tunnels
  • Mechanical & boiler rooms
  • Industrial plants
  • Commercial buildings

Application guides

Application Demonstrations

An interactive example of how the instrument is used. Try the Normal, Warning and Alarm conditions.

Indoor air & car park

Car park carbon monoxide

Measure carbon monoxide so the ventilation system knows when fresh air is needed.

Illustration: Car park carbon monoxide, with numbered measurement points
Illustrative simulation — not live instrument data. The interactive version needs JavaScript.

Illustrative simulation — not live instrument data.

Measurement points

  1. CM50 on the column
  2. Extract fans switched by the BMS

Monitoring workflow

  1. CM50 is wall- or conduit-mounted in the car park.
  2. It measures 0–1000 or 0–2000 ppm CO with ±5 ppm accuracy.
  3. The value is output as 4–20 mA, 0–10 V or RS485.
  4. The BMS switches the extract fans according to its own settings.

Products used

  • CM50 CO (Carbon Monoxide) Transmitter This product

Fan switching is a function of the BMS. CO levels and fan stages shown are examples.

Documents and software

Related products

Enquiry

Ask about the CM50 CO (Carbon Monoxide) Transmitter

Tell us what you need to measure, the range and the installation. Our technical team will reply with a recommendation and quotation.

Fields marked * are required.