Polwax Global

CO₂ & CO Transmitters

CD50 CO₂ Transmitter

CD50 (CarbonDio50)

Carbon dioxide transmitter with 0–2000, 0–5000 or 0–10000 ppm range and 4–20 mA, 0–10 V or RS485 Modbus RTU output.

Range
0–2000 / 5000 / 10000 ppm
Resolution
1 ppm
Outputs
4–20 mA, 0–10 V, RS485
Protection
IP65

Overview

Available as 3 versions: CD50-101, CD50-102 and CD50-103.

Typical applications: indoor air quality – offices, schools, public spaces, greenhouse climate control, industrial safety in confined spaces.

Key features

  • Ranges 0–2000, 0–5000 or 0–10000 ppm
  • Resolution 1 ppm, data update every 2 s
  • 4–20 mA, 0–10 V or RS485 Modbus RTU output
  • Wall or pole mounting, IP65

Technical specifications

Measurement ranges & outputs
Measurement range0 - 2000 ppm (code 101) / 0 - 5000 ppm (code 102) / 0 - 10000 ppm (code 103)
Accuracy5000 ppm: ±(50 ppm + 3 % F·S) (25 °C) · 10000 ppm: ±(50 ppm + 5 % F·S) (25 °C)
Resolution1 ppm
Stability<2 % F·S
Non-linearity<1 % F·S
Data update2 s
Warm-up time2 min (available), 10 min (max.)
Output (order code)0-10 V, RS485 Modbus RTU, 4-20 mA
Power supply & connectivity
Power supply12 V – 24 V DC
Installation & environment
Mounting optionsWall mount, pole mount
Housing materialIndustrial-grade ABS
Protection ratingIP65 (water-resistant and dustproof)
Humidity range0–95 % RH (non-condensing)

Specifications are subject to change. Please check the current datasheet or ask our team before ordering.

Models and ordering information

ModelDescription
CD50-1010 - 2000 ppm measurement range
CD50-1020 - 5000 ppm measurement range
CD50-1030 - 10000 ppm measurement range

Applications and industries

  • Indoor air quality – offices, schools, public spaces
  • Greenhouse climate control
  • Industrial safety in confined spaces

Application guides

Application Demonstrations

Interactive examples of how this instrument is used. Choose an application, then try the Normal, Warning and Alarm conditions.

Indoor air & car park

Indoor air quality (CO₂)

Track room CO₂ rising with occupancy so ventilation can respond to the people present.

Illustration: Indoor air quality (CO₂), with numbered measurement points
Illustrative simulation — not live instrument data. The interactive version needs JavaScript.

Illustrative simulation — not live instrument data.

Measurement points

  1. CD50 on the meeting-room wall
  2. Supply-air diffuser (ventilation controlled by the BMS)

Monitoring workflow

  1. CD50 measures CO₂ with a range of 0–2000, 0–5000 or 0–10000 ppm and 1 ppm resolution.
  2. Data updates every 2 seconds.
  3. Outputs: 4–20 mA, 0–10 V or RS485 Modbus RTU (order code).
  4. The ventilation system or BMS adjusts airflow according to its own settings.

Products used

  • CD50 CO₂ Transmitter This product

Occupancy, CO₂ values and limits are illustrative.

Outdoor, solar & greenhouse

Greenhouse light for plants (PAR)

Measure plant-usable light at 400–700 nm to decide when grow lights are needed.

Illustration: Greenhouse light for plants (PAR), with numbered measurement points
Illustrative simulation — not live instrument data. The interactive version needs JavaScript.

Illustrative simulation — not live instrument data.

Measurement points

  1. PAR50 at canopy level
  2. Grow lights switched by the climate computer

Monitoring workflow

  1. PAR50 is placed at canopy level.
  2. It measures 0 to 2500 µmol/m²·s over 400–700 nm, ±3 % full scale.
  3. Outputs: 4–20 mA, 0–10 V or RS485 Modbus RTU.
  4. The climate computer switches grow lights according to its own settings.

Products used

Light values, crop set-points and the grow-light rule are illustrative.

Related products

Enquiry

Ask about the CD50 CO₂ Transmitter

Tell us what you need to measure, the range and the installation. Our technical team will reply with a recommendation and quotation.

Fields marked * are required.