CO₂ & CO Transmitters
CM50 CO (Carbon Monoxide) Transmitter
CM50
Industrial carbon monoxide gas detector and transmitter, 0–1000 or 0–2000 ppm, ±5 ppm accuracy, for car parks, tunnels and plant rooms.
- Range
- 0–1000 / 0–2000 ppm
- Accuracy
- ±5 ppm
- Outputs
- 4–20 mA, 0–10 V, RS485
- Supply
- 10–30 V DC
Overview
Available as 2 versions: CM50-101 and CM50-102.
Typical applications: underground parking garages, tunnels, mechanical & boiler rooms, industrial plants, commercial buildings.
Key features
- Ranges 0–1000 or 0–2000 ppm
- Accuracy ±5 ppm, resolution 1 ppm
- 4–20 mA, 0–10 V or RS485 Modbus RTU output
- Optional OLED display
- Sensor lifespan up to 5 years
Technical specifications
| Measurement range | 0 - 1000 ppm (code 101) / 0 - 2000 ppm (code 102) |
|---|---|
| Accuracy | ±5 ppm |
| Resolution | 1 ppm |
| Response time | ≤30 seconds |
| Repeatability | ≤2 % of signal value |
| Zero drift | ±3 ppm |
| Long-term drift | ≤2 % |
| Output (order code) | 0-10 V, RS485, 4-20 mA |
| Sensor lifespan | Up to 5 years |
| Display | Optional OLED display |
|---|
| Power supply | 10–30 V DC |
|---|
| Installation method | Wall-mounted / conduit-mount |
|---|---|
| Operating temperature | -20 °C to 50 °C |
| Operating humidity | 15–90 % RH (non-condensing) |
| Pressure range | 90–110 kPa |
Specifications are subject to change. Please check the current datasheet or ask our team before ordering.
Models and ordering information
| Model | Description |
|---|---|
| CM50-101 | 0–1000 ppm measurement range |
| CM50-102 | 0–2000 ppm measurement range |
Applications and industries
- Underground parking garages
- Tunnels
- Mechanical & boiler rooms
- Industrial plants
- Commercial buildings
Application guides
-
Car park carbon monoxide
Measure carbon monoxide so the ventilation system knows when fresh air is needed.
Application Demonstrations
An interactive example of how the instrument is used. Try the Normal, Warning and Alarm conditions.
Indoor air & car park
Car park carbon monoxide
Measure carbon monoxide so the ventilation system knows when fresh air is needed.
Illustrative simulation — not live instrument data.
Measurement points
- CM50 on the column
- Extract fans switched by the BMS
Monitoring workflow
- CM50 is wall- or conduit-mounted in the car park.
- It measures 0–1000 or 0–2000 ppm CO with ±5 ppm accuracy.
- The value is output as 4–20 mA, 0–10 V or RS485.
- The BMS switches the extract fans according to its own settings.
Products used
CM50 CO (Carbon Monoxide) Transmitter This product
Fan switching is a function of the BMS. CO levels and fan stages shown are examples.
Documents and software
Related products

CD50 (CarbonDio50)
CD50 CO₂ Transmitter
Carbon dioxide transmitter with 0–2000, 0–5000 or 0–10000 ppm range and 4–20 mA, 0–10 V or…

SL50
SL50 Sound Level Transmitter
Noise transmitter measuring 30–120 dB at ±1.5 dB accuracy, with 4–20 mA, 0–10 V or RS485…

RHT50 WM
RHT50 WM Temperature & Humidity Transmitter
Wall-mount temperature and humidity transmitter: ±0.4 °C, ±1.8 % RH, two analogue outputs, RS485 Modbus RTU,…

RHT100
ClimaTRANS RHT100 Temperature & Humidity Transmitter
Industrial temperature and humidity transmitter with TFT display, RS485 Modbus RTU and wall or duct mounting.
Enquiry
Ask about the CM50 CO (Carbon Monoxide) Transmitter
Tell us what you need to measure, the range and the installation. Our technical team will reply with a recommendation and quotation.